Door Fan Test (Blower Door) for FM200 Clean Agent Protected Enclosure
Publisher:chuge8 Time:2017/8/18 11:21:06 Browse:2060
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
|
One of the top Invest Banks with HQ in Switzerland asked us to provide Door Fan Test (Blower Door) for their new MER room located at a office building as a acceptance procedure. We conducted the test and found it failed to the test. After further inspection with our dedicated leakage indentifying tool, we found that the MER has three floors, and the partition walls were connected from the second floor and below the second floor the MER and the other rooms shared the same space. It is hard to indentify the leakage without the dedicated leakage indentifying tools.
|
|
|